Title: | CONTROL OF SHUNT ACTIVE POWER FILTER UNDER ADVERSE GRID CONDITIONS |
Authors: | KAUR, SIMAR PREET |
Keywords: | GRID CONDITIONS DOUBLE SECOND ODER GENERALIZAED INTEGRATOR (DSOGI) SHUNT ACTIVE POWER FILTER (SAPF) SYNCHRONOUS REFERENCE FRAME (SRF) UNIT TEMPLATE (UT) DSOGI |
Issue Date: | 2020 |
Publisher: | DELHI TECHNOLOGICAL UNIVERSITY |
Series/Report no.: | TD - 5339; |
Abstract: | This report discusses the design together with the application of a Double Second Order Generalized Integrator (DSOGI) for grid integration. A moderately distorted supply (having a THD equal to 8.49 %) feeds a non – linear load and a Shunt Active Power Filter (SAPF) is used as a compensator. In this report, two different control approaches have been used to derive reference currents for the SAPF. These algorithms are the Unit Template (UT) based controller and Synchronous Reference Frame (SRF) theory – based approach. Both the algorithms fail to achieve less than 5 % distortion in supply currents when used under distorted / polluting grid conditions. Hence a DSOGI based controller has been realized to generate perfectly sinusoidal reference currents even under adverse grid conditions. With the proposed modification in the controller design using the DSOGI block, perfectly sinusoidal grid currents can be generated. System has been simulated in the MATLAB environment using SIMULINK and PSB toolboxes. Performance results demonstrate the effectiveness of DSOGI based non – phase locked loop approach for grid synchronization. |
URI: | http://dspace.dtu.ac.in:8080/jspui/handle/repository/18809 |
Appears in Collections: | M.E./M.Tech. Electrical Engineering |
Files in This Item:
File | Description | Size | Format | |
---|---|---|---|---|
Thesis_report_Simar_Preet_Kaur_2K17PSY17.pdf | 4.59 MB | Adobe PDF | View/Open |
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.