    <title>USE OF ECOFRIENDLY IN LOW TEMPERATURE CIRCUIT IN TERMS OF FIRST LAW AND SECOND LAW EFFICIENCY OF THREE STAGES CASCADE REFRIGERATION OF BIOMEDICAL APPLICATIONS</title>
    <link>http://dspace.dtu.ac.in:8080/jspui/handle/repository/15362</link>
    <description>Title: USE OF ECOFRIENDLY IN LOW TEMPERATURE CIRCUIT IN TERMS OF FIRST LAW AND SECOND LAW EFFICIENCY OF THREE STAGES CASCADE REFRIGERATION OF BIOMEDICAL APPLICATIONS
Authors: MISHRA, R.S.
Abstract: Biomedical preservation requires storing biological specimens like stem cells blood and organs, at a&#xD;
storage temperature below -95oC, Hence, the main aim of the current research is to conduct a&#xD;
thermodynamic energy and exergy analysis to determine the thermal performance of three stages&#xD;
cascade refrigeration systems in the high temperature condenser temperature using R1234ze and&#xD;
R1234yf in high temperature circuit of condenser temperature of 70oC and zero degree centrigade of&#xD;
first evaporator temperature in High temperature circuit, and evaporator temperature(-80oC) in&#xD;
intermediate circuit using R134a and R410a as ecofriendly refrigerants is investigated. For low&#xD;
temperature evaporator temperature (-135oC) using hydrocarbons (R290, R600 and R600a), R404aand&#xD;
other refrigerants in low temperature evaporator circuit on system performances (i.e. overall system&#xD;
coefficient of performance, (first law efficiency), exergetic efficiency (second law efficiency) and system&#xD;
exergy destruction ratio (EDR) is investigated in three stages /four stages cascade refrigeration systems&#xD;
are shown in this paper.</description>